UHF PD Sensor UHF-DN50/DN80

The UHF PD sensor DN50 / DN80 is suitable for measuring of electromagnetic radiation by internal  partial discharges (PD) in the ultra-high frequency (UHF) range in transformers. The sensor can be inserted via standardized DN50 and DN80 gate valves into the transformer tank. This can be done even if the transforer is in service. This type of sensor is typically used for diagnostic PD measurements and can also be used for permanent monitoring of PD. The advantage of UHF measurements compared to conventional electric measurements is its selectivity: high external noise which often occurs at onsite measurements have only little effect on internal UHF PD measurements.